Rating (VA/W) 1500VA/1500W
Format RT2U (tower/rack 2U)
Electrical Characteristics
Technology Line-Interactive High Frequency (Pure Sinewave, Booster + Fader)
Input voltage range without batteries 160V-294V (adjustable to 150V-294V)
Input frequency range without batteries 47 to 70 Hz (50Hz system), 56.5 to 70Hz (60Hz system), 40Hz in low-sensitivity mode
Output voltage 230V (+6/-10%)(Adjustable to 200V*/208V/220V/230V/240V), 50/60 Hz +/-0.1 Hz (autosensing)
Connections      
Input IEC C14 (10A)
Output (8) IEC C13 (10A)
Remote controlled sockets 2 groups of (2) IEC C13 (10A)
Batteries
Typical Backup Times** 300W
5PX 1500 44
Battery management ABM® Temperature compensated charging method (user selectable). Automatic battery test, deep discharge protection, automatic recognition of external battery units
Interfaces
Communication ports 1 USB port + 1 serial RS232 port + 1 mini-terminal block for Remote ON/OFF + 1 mini-terminal block for Remote Power OFF + 1 mini-terminal block for output relay
Communication slot 1 slot for Network-M2, INDGW-M2, or RELAY-MS cards
Operating conditions, standards and approvals
Operating temperature 0 to 40°C
Noise level
Safety IEC/EN 62040-1, UL1778, CSA22.2
EMC, Performance IEC/EN 62040-2, FCC Class B, CISPR22 Class B
Approvals CE / CB report (TUV) / cTUVus / EAC / UKCA / Ukr / Cm / RCM
Dimensions W x D x H / Weight      
UPS Dimensions (mm) 438x448x85.5
UPS Weight (kg) 22.4
EBM dimensions (mm) 438x448x85.5
EBM weight (kg) 27.8
Customer Service & Support  
Warranty 3 years (See ANZ Warranty Statement)
*5% derating @ 200V