Rating (VA/W) 2000VA/2000W   
Format RT2U (tower/rack 2U)  
Electrical Characteristics      
Technology Line-Interactive High Frequency (Pure Sinewave, Booster + Fader)    
Input voltage range without batteries 160V~294V (adjustable to 150V~294V)     
Input frequency range without batteries 47~70Hz (50Hz system), 56.5~70Hz (60Hz system), 40Hz in low-sensitivity mode    
Output voltage 230V (+6/-10%) (Adjustable to 200V*/208V/220V/230V/240V), 50/60Hz +/-0.1Hz (autosensing)   
Connections      
Input IEC C14 (10A)
Output (8) IEC C13 (10A)
Remote-controlled sockets 2 groups of (2) IEC C13 (10A) 
Batteries      
Typical Backup Times** 500W
5PX 1500 24 
5PX 1500 + 1 EBM / 4 EBM 92/346 
5PX 2000 28
5PX 2000 + 1 EBM / 4 EBM 138/551
5PX 2200 28
5PX 2200 + 1 EBM / 4 EBM 138/551  
5PX 3000 39
5PX 3000 + 1 EBM / 4 EBM 146/546
Battery management ABM® Temperature-compensated charging method (user selectable). Automatic battery test, deep discharge protection, automatic recognition of external battery units
Interfaces      
Communication ports 1 USB port + 1 serial RS232 port + 1 mini-terminal block for Remote ON/OFF + 1 mini-terminal block for Remote Power OFF + 1 mini-terminal block for output relay
Communication slot 1 slot for Network-M2, INDGW-M2, or RELAY-MS cards     
Operating conditions, standards and approvals      
Operating temperature 0°C~40°C     
Noise level  <40dB @ typical load
Safety IEC/EN 62040-1, UL1778, CSA22.2     
EMC, Performance IEC/EN 62040-2, FCC Class B, CISPR22 Class B     
Approvals CE / CB report (TUV) / cTUVus / EAC / UKCA / Ukr / Cm / RCM    
Dimensions W x D x H / Weight      
UPS Dimensions (mm) 438x603x85.5mm
UPS Weight (kg) 28kg  
EBM dimensions (mm) 438x603x85.5mm 
EBM weight (kg) 40.4kg
Customer Service & Support      
Warranty 3 years (See ANZ Warranty Statement)     
*5% derating @ 200V       
**Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.