Technical specifications
  3000
Rating (VA/W) 3000VA/3000W
Format RT2U or RT3U
Electrical Characteristics      
Technology Line-Interactive High Frequency (Pure Sinewave, Booster + Fader)
Input voltage range without batteries 160V-294V (adjustable to 150V-294V)
Input frequency range without batteries 47 to 70 Hz (50Hz system), 56.5 to 70Hz (60Hz system), 40Hz in low-sensitivity mode
Output voltage 230V (+6/-10%)(Adjustable to 200V*/208V/220V/230V/240V), 50/60 Hz +/-0.1 Hz (autosensing)
Connections      
Input IEC C20 (16A)
Output (8) IEC C13 (10A)
(2) IEC C19 (16A)
Remote controlled sockets  
BatteriesTypical Backup Times**            
300W 500W 800W 1200W 1800W 2500W
5PX 1500 44 24 13 7    
5PX 1500 + 1 EBM / 4 EBM 164/611 92/346 53/199 33/123    
5PX 2000 50 28 16 9 4  
5PX 2000 + 1 EBM / 4 EBM 242/958 138/551 80/319 49/197 30/121  
5PX 2200 50 28 16 9 4  
5PX 2200 + 1 EBM / 4 EBM 242/958 138/551 80/319 49/197 30/121  
5PX 3000 68 39 23 13 7 4
5PX 3000 + 1 EBM / 4 EBM 255/950 146/546 86/323 54/201 33/124 22/84
Battery management ABM®  Temperature-compensated charging method (user selectable). Automatic battery test, deep discharge protection, automatic recognition of external battery units
Interfaces      
Communication ports 1 USB port + 1 serial RS232 port + 1 mini-terminal block for Remote ON/OFF + 1 mini-terminal block for Remote Power OFF + 1 mini-terminal block for output relay
Communication slot 1 slot for Network-M2, INDGW-M2, or RELAY-MS cards
Operating conditions, standards and approvals      
Operating temperature 0 to 40°C
Noise level 
Safety IEC/EN 62040-1, UL1778, CSA22.2
EMC, Performance IEC/EN 62040-2, FCC Class B, CISPR22 Class B
Approvals CE / CB report (TUV) / cTUVus / EAC / UKCA / Ukr / Cm / RCM
Dimensions W x D x H / Weight      
UPS Dimensions (mm) 438x603x85.5 (RT2U)
438x483x129 (RT3U)
UPS Weight (kg) 31.7 (RT2U) / 31.1 (RT3U)
EBM dimensions (mm) 438x603x85.5 (RT2U)
438x483x129 (RT3U)
EBM weight (kg) 40.4 (RT2U) / 39.7 (RT3U)
Customer Service & Support      
Warranty 3 years (See ANZ Warranty Statement)     
*5% derating @ 200V      
**Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
In the interest of continuous product improvement, all specifications are subject to change without notice.
* All 5PX UPS and EBM are delivered with rack kit