Capacity |
2000VA/1800W |
Topology |
True online double- conversion,Pure Sine Wave |
INPUT |
Voltage Range |
Low Line Transfer |
160Vac / 140Vac / 120 / 110Vac ± 5 % (based on load percentage 100%-80% / 80%-70% / 70%-60% / 60%-0) |
Low Line Comeback |
175Vac / 155Vac / 135Vac / 125Vac ± 5 % |
High Line Transfer |
300Vac ± 5 % |
High Line Comeback |
290Vac ± 5 % |
Frequency Range |
40Hz - 70Hz |
Phase |
Single phase with ground |
Power Factor Correction |
>0.99 @ nominal voltage (100% load) |
OUTPUT |
Output Power Factor |
0.9 |
Output Voltage (AC Mode) |
240Vac (Selectable 200/208/220/230/240Vac) |
Voltage Regulation (Batt. Mode) |
± 1% |
Frequency Range (Batt. Mode) |
50Hz or 60Hz ±1Hz |
Current Crest Ratio |
3:1 (max.) |
Transfer |
AC Mode to Batt. Mode |
Zero |
Inverter to Bypass |
4ms (Typical) |
Waveform (Batt. Mode) |
Pure Sine Wave |
EFFICIENCY |
ECO Mode (Advanced) |
97% |
Battery Mode |
87% |
BATTERY |
Battery Number (12 V*9AH) |
x 6 |
Typical Recharge Time |
4 hours recover to 90% capacity (for standard model only) |
Charging Current (max.) |
Standard Models - 1.5Amp. Long Run Models - 1Amp / 2Amp / 4Amp / 6Amp selectable (factory default is 6Amp) |
PROTECTION |
Full Protection |
Overload, discharge, thermal, short circuit and overcharge protection |
Surge Protection |
984 Joules / 22000 Amps |
COMMUNICATIONS AND MANAGMENT |
Interface |
USB or RS232 as standard, Intelligent slot for PSSNMP, PSModbus or PSAS400 dry contact |
Software |
PowerShield® NetGuard® software - supports Windows, Linux, Unix and Mac based operating systems |
LCD Display/Alarm |
UPS Status, Load & Battery Level, Input/Output Voltage, Batt. Time Remaining and Fault Indicators |
Audible Alarm |
Battery Mode, Bypass Mode, Low Battery (Batt. Mode), Fault, Overload |
PHYSICAL |
Dimension, (D x W x H) mm |
600 x 438 x 88 |
Weight (kg) |
26.8 & 10.5 |
OPERATING ENVIRONMENT |
Temperature |
0 - 40°C |
Humidity |
20 - 90% (RH Non-condensing) |
Noise Level |
< 50dBA @ 1 Meter |
COMPLIANCE |
Safety / EMC / RoHS |
EN62040-1-1 2003, IEC60950-1-1 / EN62040-2 2006 / Directive 2011/65/EU |