INPUT  

Voltage Range Line Loss 110V~300V AC@(0~60%) Load; 140V~300V @(60~80%) Load; 176V~300V AC@(80~100%) Load
Low Line Comeback  Low Line Loss Voltage +10V
High Line Comeback High Line Loss Voltage -10V
Frequency Range  46Hz~54Hz@50Hz system; 56Hz~64Hz@60Hz system
Phase Single phase with ground
Power Factor Correction ≤0.99@nominal voltage (100% load)

OUTPUT

Output Power Factor: 0.9
Output Voltage 208/220/230/240V AC Selectable
AC Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46Hz~54Hz@50Hz system
56Hz~64Hz@60Hz system
Frequency Range (Batt. Mode) 50Hz±0.1Hz or 60Hz±0.1Hz
Overload AC Mode: 100%~110%: 10min; 110%~130%: 1min; >130%: 1sec
Battery Mode: 100%~110%: 30sec; 110%~130%: 10sec; >130%: 1sec
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≤1% @ 100% Linear Load; ≤4% @100% Non-linear Load
Transfer Time Line to Battery: 0ms
Inverter to Bypass: 0ms
Inverter to Eco: < 10ms

EFFICIENCY 

ECO Mode (Advanced) <94%
Battery Mode <93%

BATTERY 

Battery Number Optional strings of 16 or 20 batteries
Typical Recharge Time According to an external battery pack
Charging Current (max.) 4A ± 10%

COMMUNICATIONS & MANAGEMENT 

Interface USB and RS232 as standard
Software PowerShield® NetGuard® software - supports Windows, Linux, Unix and Mac based operating systems
Optional Intelligent slot for PSSNMPV4, PSModbus or PSAS400 dry contact

PHYSICAL 

Dimensions (D x W x H) UPS Unit: 600x438x88mm [2U] (weight: 17kg)
PSRTBB16 (16 batteries): 688x438x88mm [2U] (weight: 48kg)
PSRTBB20 (20 batteries): 607x438x133mm [3U] (weight: 60kg)

OPERATING ENVIRONMENT 

Temperature 0°C~40°C
Humidity 95% (RH Non-condensing)
Altitude <1000m
Noise Level Less than 55dB@1m