INPUT |
||
Voltage Range | Line Loss | 110V~300V AC @(0~60%) Load; 140V~300V @(60~80%) Load; 176V~300V AC @(80~100%) Load |
Low Line Comeback | Low Line Loss Voltage +10V | |
High Line Comeback | High Line Loss Voltage -10V | |
Frequency Range | 46Hz~54Hz@50Hz system; 56Hz~64Hz@60Hz system | |
Phase | Single phase with ground | |
Power Factor Correction | ≤0.99@nominal voltage (100% load) | |
OUTPUT |
Output Power Factor: 0.9 | |
Output Voltage | 208/220/230/240V AC Selectable | |
AC Voltage Regulation | ±1% | |
Frequency Range (Synchronized Range) | 46Hz~54Hz@50Hz system 56Hz~64Hz@60Hz system |
|
Frequency Range (Batt. Mode) | 50Hz±0.1Hz or 60Hz±0.1Hz | |
Overload | AC Mode: 100%~110%: 10min; 110%~130%: 1min; >130%: 1sec Battery Mode: 100%~110%: 30sec; 110%~130%: 10sec; >130%: 1sec |
|
Current Crest Ratio | 3:1 (max.) | |
Harmonic Distortion | ≤1 % @ 100% Linear Load; ≤4% @100% Non-linear Load | |
Transfer Time | Line to Battery: 0ms Inverter to Bypass: 0ms Inverter to Eco: < 10ms |
|
EFFICIENCY |
||
ECO Mode (Advanced) | <94% | |
Battery Mode | <93% | |
BATTERY |
||
Battery Number | Optional strings of 16 or 20 batteries | |
Typical Recharge Time | According to an external battery pack | |
Charging Current (max.) | 4A ± 10% | |
COMMUNICATIONS & MANAGEMENT |
||
Interface | USB and RS232 as standard | |
Software | PowerShield® NetGuard® software - supports Windows, Linux, Unix and Mac based operating systems | |
Optional | Intelligent slot for PSSNMPV4, PSModbus or PSAS400 dry contact | |
PHYSICAL |
||
Dimensions (D x W x H) | UPS Unit: 600x438x88mm [2U] (weight: 20kg) PSRTBB16 (16 batteries): 688x438x88 [2U] (weight: 48kg) PSRTBB20 (20 batteries): 607x438x133 [3U] (weight: 60kg) |
|
OPERATING ENVIRONMENT |
||
Temperature | 0°C~40°C | |
Humidity | 95% (RH Non-condensing) | |
Altitude | <1000m | |
Noise Level | Less than 58dB@1m |