Capacity 2000VA/1800W
Topology True online double- conversion, Pure Sine Wave
Input
Voltage Range

Low Line Transfer: 160Vac/140Vac/120/110Vac ±5% (based on load percentage 100%-80%/80%-70%/70%-60%/60%-0)

Low Line Comeback: 175Vac/155Vac/135Vac/125Vac ±5 %

High Line Transfer: 300Vac ±5 %

High Line Comeback: 290Vac ±5 %

Frequency Range 40Hz - 70Hz
Phase Single-phase with ground
Power Factor Correction ≤0.99 @ nominal voltage (100% load)
Output
Output Power Factor 0.9
Output Voltage (AC Mode) 240Vac (Selectable 200/208/220/230/240Vac)
Voltage Regulation (Batt. Mode) ±1%
Frequency Range (Batt. Mode) 50Hz or 60Hz ±1Hz
Current Crest Ratio 3:1 (max.)
Transfer

AC Mode to Batt. Mode: 0
Inverter to Bypass: 4ms (Typical)

Waveform (Batt. Mode)

Pure Sine Wave

Efficiency
ECO Mode (Advanced) 97%
Battery Mode 87%
Battery
Battery Number (12 V*9AH) x4
Typical Recharge Time 4 hours recover to 90% capacity (for standard model only)
Charging Current (max.) Standard Models - 1.5Amp. Long Run Models - 1Amp/2Amp/4Amp/6Amp selectable (factory default is 6Amp)
Protection
Full Protection Overload, discharge, thermal, short circuit and overcharge protection
Surge Protection 984 Joules/22000 Amps
Communications and Management
Interface USB or RS232 as standard, Intelligent slot for PSSNMP, PSModbus or PSAS400 dry contact
Software PowerShield® NetGuard® software - supports Windows, Linux, Unix and Mac-based operating systems
LCD Display/Alarm UPS Status, Load & Battery Level, Input/Output Voltage, Batt. Time Remaining and Fault Indicators
Audible Alarm Battery Mode, Bypass Mode, Low Battery (Batt. Mode), Fault, Overload
Physical
Dimension, (D x W x H) mm 500 x 438 x 88
Weight (kg) 19.5
Operating Environment
Temperature 0°C ~ 40°C
Humidity 20% ~ 90% (RH Non-condensing)
Noise Level <50dBA@1m
Compliance  
Safety/EMC/RoHS EN62040-1-1 2003, IEC60950-1-1/EN62040-2 2006/Directive 2011/65/EU