Capacity | 2000VA/1800W |
Topology | Line Interactive, Pure Sine Wave |
Input | |
Voltage | 240Vac (Nominal) |
Voltage Range | 162-290V ac |
Frequency Range | 50/60Hz (Auto-sensing) ±5Hz |
Output | |
Output Voltage (AC Mode) | 240V ac (Selectable 208/220/230Vac) ±10% AVR |
Voltage Regulation (Batt. Mode) | ±3% |
Frequency Range (Batt. Mode) | 50Hz or 60Hz ±1Hz |
Current Crest Ratio | 3:1 |
Transfer Time | 6ms (Typical) |
Waveform (Batt. Mode) | Pure Sine Wave |
Efficiency | |
ECO Mode (Advanced) | 98% |
Battery Mode | 89% |
Battery | |
Standard Model | Battery Type & Number: 12V x 9AH (x 4) Typical Recharge Time: 4 hours to recover to 90% capacity |
Additional Battery Banks | PSRTBB8 (x1) |
Protection | |
Full Protection | Overload, discharge, thermal, short circuit and overcharge protection |
Surge Protection | 1560J/32500A |
Communications & Management | |
Interface | USB or RS232 as standard, Intelligent slot for PSSNMP, PSModbus or PSAS400 dry contact |
Software | PowerShield NetGuard® software - supports Windows based operating systems, Linux, Unix and Mac |
LCD Display/Alarm | AC Mode, Batt.Mode, Load Level, Input Voltage, Output Voltage, Overload, Fault, Low Batt, Batt.Time Remaining |
Audible Alarm | Battery Mode, Low Battery (Batt. Mode), Fault, Overload |
Physical | |
Dimension (D x W x H) | 480 x 438 x 88mm |
Weight (Net/Gross) | (23kg/25kg) |
Operating Environment | |
Temperature | 0 - 40°C |
Humidity | 0 - 90% (RH Non-condensing) |
Noise Level | <45dB |
Compliance | |
Safety | EN62040-1-1 2003, IEC60950-1-1 |
EMC | EN62040-2 2006 |
RoHS | Directive 2011/65/EU |