PSCERT1000L RT BATTERY BANKS: PSRTBB12
Capacity 1000VA/900W   
Topology True online double- conversion, Pure Sine Wave  
INPUT
Voltage Range Low Line Transfer 160V/140V/120V/110V AC ±5% (based on load percentage 100%-80%/80%-70%/70%-60%/60%-0)  
Low Line Comeback 175V/155V/135V/25V AC ±5%  
High Line Transfer 300V AC ±5%  
High Line Comeback 290V AC ±5%  
Frequency Range 40Hz ~ 70Hz  
Phase Single phase with ground  
Power Factor Correction  ≥0.99 @ nominal voltage (100% load)  
OUTPUT
Output Power Factor 0.9  
Output Voltage (AC Mode) 240V AC (Selectable 200/208/220/230/240V AC)  
Voltage Regulation (Batt. Mode) ± 1%  
Frequency Range (Batt. Mode) 50Hz or 60Hz ±1Hz  
Current Crest Ratio 3:1 (max.)  
Transfer AC Mode to Batt. Mode 4ms (Typical)  
Inverter to Bypass Pure Sine Wave  
EFFICIENCY
ECO Mode (Advanced) 96%  
Battery Mode 86%  
BATTERY
Battery Number (12Vx9AH) x 3  
Typical Recharge Time 4 hours recover to 90% capacity (for the standard model only)  
Charging Current (max.) Standard Models - 1.5Amp. Long Run Models - 1Amp/2Amp/4Amp/6Amp selectable (factory default is 6Amp)  
PROTECTION
Full Protection Overload, discharge, thermal, short circuit and overcharge protection  
Surge Protection 984 Joules/22000A  
COMMUNICATIONS AND MANAGEMENT
Interface USB or RS232 as standard, Intelligent slot for PSSNMP, PSModbus or PSAS400 dry contact  
Software PowerShield® NetGuard® software - supports Windows-based operating systems, Linux, Unix and Mac  
LCD Display/Alarm UPS Status, Load & Battery Level, Input/Output Voltage, Batt. Time Remaining and Fault Indicators  
Audible Alarm Battery Mode, Bypass Mode, Low Battery (Batt. Mode), Fault, Overload  
PHYSICAL
Dimension, (D x W x H) 380 x 438 x 88mm 480 x 438 x 88mm
Weight 8.4kg 22kg
OPERATING ENVIRONMENT 
Temperature 0°C ~ 40°C  
Humidity 20% ~ 90% (RH Non-condensing)  
COMPLIANCE
Safety/EMC/RoHS EN62040-1-1 2003, IEC60950-1-1/EN62040-2 2006/Directive 2011/65/EU