INPUT  

Voltage Range Low Line Transfer 160Vac / 140Vac / 120Vac / 110Vac ± 5%
(based on load percentage 100% - 80% /
80% - 70% / 70% - 60% / 60% - 0)
Low Line Comeback  170Vac / 150Vac / 130Vac / 120Vac ± 5%
High Line Transfer 300Vac ± 5%
High Line Comeback 290Vac ± 5%
Frequency Range  40Hz - 70Hz
Phase Single phase with ground
Power Factor Correction >0.99 @ nominal voltage (100% load)

OUTPUT

Output Power Factor: 0.9
Output Voltage (AC Mode) 240Vac (Selectable 208/220/230/240Vac)
Voltage Regulation (Bat. Mode) ±1%
Frequency Range (Batt. Mode) 50Hz or 60Hz ±1Hz
Current Crest Ratio 5:1 (max.)
Transfer Time 4ms (Typical)

EFFICIENCY 

ECO Mode (Advanced) 98%
Battery Mode 86%

BATTERY 

Battery Type & Number 12 V*9AH (x3)
Typical Recharge Time 4 hours recover to 90% capacity
Charging Current (max.) Standard Model -1.5Amp, Long Run Model -
1Amp/2Amp /4Amp/6Amp (factory default is 6Amp)

PROTECTION 

Full Protection Overload, discharge, thermal,
short circuit and overcharge protection
Surge Protection 984 Joules / 22000 Amps

COMMUNICATIONS & MANAGEMENT 

Interface USB or RS232 as standard, Intelligent slot
for PSSNMP, PSModbus or PSAS400 dry contact
Software PowerShield NetGuard® software -
supports Windows based operating systems,
Linux, Unix and Mac
LCD Display/Alarm UPS Status, Load & Battery Level,
Input/Output Voltage, Batt. Time
Remaining and Fault Indicators
Audible Alarm Battery Mode, Bypass Mode, Low Battery (Batt. Mode),
Fault, Overload

PHYSICAL 

Dimension (D x W x H) 480 x 438 x 88 mm
Weight 18kg

OPERATING ENVIRONMENT 

Temperature 0 - 40°C
Humidity 20 - 90% (RH Non-condensing)
Noise Level < 50dBA @ 1 Meter

COMPLIANCE 

Safety EN62040-1-1 2003, IEC60950-1-1
EMC EN62040-2 2006
RoHS Directive 2011/65/EU