INPUT

Voltage Range Low Line Transfer 176VAC @ 100% load
110VAC @ 50% load
Low Line Comeback  186VAC @ 100% load
120VAC @ 50% load
High Line Transfer 300VAC
High Line Comeback 290VAC
Frequency Range  46Hz~54Hz " 50Hz / 56Hz~64Hz " 60Hz
Phase Single phase with ground
Power Factor 0.99 @ 100%load

OUTPUT

AC Voltage Regulation (Batt. Mode)  ± 1%
Frequency Range (Synchronized Range)  46Hz ~ 54Hz 50Hz/56Hz~64Hz 60Hz
Frequency Range (Batt.Mode) 50Hz ± 0.1Hz or 60Hz ± 0.1Hz
Load Crest Factor 3:1
Harmonic Distortion 2% THD (Linear Load)
6% THD (Linear Load)
Transfer AC Mode to Batt. Mode  Zero
Inverter to Bypass Zero
Waveform (Batt. Mode) Pure Sinewave

EFFICIENCY 

ECO Mode 90%
Battery Mode 88%
BATTERY  
Battery Type 12Vx9AH (x20)
Typical Recharge Time 7 hours recover to 90% capacity
Charging Current (Max.) 1.0A
Charging Voltage 273.0 VDC

PROTECTION 

Full Protection Overload, discharge, thermal,
short circuit and overcharge protection

COMMUNICATIONS & MANAGEMENT 

Interface USB or RS232 as standard,
Intelligent slot for PSSNMP
or PSAS400 dry contact
Software Power Shield NetGuard Software -
supports Windows based operating Systems,
Linux, Unix & Mac
LCD Display / Alarm UPS Status, Load Level, Battery Level,
Input/Output Voltage, Battery Time Remaining
and Fault Indicators
Audible Alarm Battery Mode, Low Battery, Overload, Fault

PHYSICAL 

Dimension (D x W x H) 575 x 250 x 576.5mm
Weight 90kg/35kg

OPERATING ENVIRONMENT 

Temperature 0°C - 40°C
Humidity 20% - 90% (RH Non-Condensing)
Noise Level Less than 55dB @ 1 Meter

COMPLIANCE 

Safety EN62040-1-1 2003, IEC60950-1-1
EMS EN62040-2 2006
RoHS Directive 2001 / 65 / EU