INPUT  

Voltage Range    Low Line Transfer 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 %
(based on load percentage 100% - 80% / 80% - 70%
/ 70% - 60% / 60% - 0%)
Low Line Comeback  175 VAC ± 5%
High Line Transfer 300 VAC ± 5%
High Line Comeback  47.5Hz ~ 52.5 Hz or 57Hz ~ 63Hz
Frequency Range  47.5Hz ~ 52.5 Hz or 57Hz ~ 63Hz
Phase  Single Phase with Ground
Power Factor  0.98

OUTPUT  

AC Voltage Regulation
(Batt. Mode) 
± 3%
Frequency Range
(Synchronized Range) 
48Hz ~ 52Hz or 57Hz ~ 63Hz
Frequency Range
(Batt. Mode) 
50Hz ± 0.25Hz or 60Hz ± 0.3Hz
Load Crest Factor  3:1
Harmonic Distorion  4% THD (Linear Load)
7% THD (Non-linear Load)
Transfer  AC Mode to Batt. Mode  Zero
Inverter to Bypass 4ms (Typical)
Waveform (Batt. Mode) Pure Sinewave

EFFICIENCY

ECO Mode 88%
Battery Mode 83%
BATTERY
Battery Type 12Vx9AH(x6)
Typical Recharge Time 4 hours recover to 90% capacity
Charging Current (max.) 1.0A
Charging Voltage 82.1 VDC ±1%

PROTECTION

Full Protection Overload, discharge, thermal,
short circuit and overcharge protection

COMMUNICATIONS & MANAGEMENT

Interface USB or RS232 as standard,
Intelligent slot for PSSNMP or
PSAS400 dry contact
Software Power Shield NetGuard Software -
supports Windows based operating Systems,
Linux, Unix & Mac
LCD Display / Alarm UPS Status, Load Level, Battery Level,
Input/Output Voltage, Battery Time
Remaining and Fault Indicators
Audible Alarm Battery Mode, Low Battery, Overload, Fault

PHYSICAL

Dimension (D x W x H) 425 x 190 x 335mm
Weight 26kg

OPERATING ENVIRONMENT

Temperature 0°C - 40°C
Humidity 20% - 90% (RH Non-Condensing)
Noise Level Less than 45dBA @ 1 Meter

COMPLIANCE

Safety EN62040-1-1 2003, IEC60950-1-1
EMS EN62040-2 2006
RoHS Directive 2001 / 65 / EU